Fx Copy
LaTeX Copy
Zero Sequence Current consists of a balanced three-phase current, phasors of which all have the same phase angles and rotate counterclockwise together. Check FAQs
I0=-I1(Z2Z0+Z2+3Zf)
I0 - Zero Sequence Current?I1 - Positive Sequence Current?Z2 - Negative Sequence Impedance?Z0 - Zero Sequence Impedance?Zf - Fault Impedance?

Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) Example

With values
With units
Only example

Here is how the Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) equation looks like with Values.

Here is how the Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) equation looks like with Units.

Here is how the Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) equation looks like.

-2.7802Edit=-2.001Edit(-44.6Edit8Edit+-44.6Edit+31.5Edit)
You are here -

Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) Solution

Follow our step by step solution on how to calculate Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?

FIRST Step Consider the formula
I0=-I1(Z2Z0+Z2+3Zf)
Next Step Substitute values of Variables
I0=-2.001A(-44.6Ω8Ω+-44.6Ω+31.5Ω)
Next Step Prepare to Evaluate
I0=-2.001(-44.68+-44.6+31.5)
Next Step Evaluate
I0=-2.78020560747664A
LAST Step Rounding Answer
I0=-2.7802A

Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) Formula Elements

Variables
Zero Sequence Current
Zero Sequence Current consists of a balanced three-phase current, phasors of which all have the same phase angles and rotate counterclockwise together.
Symbol: I0
Measurement: Electric CurrentUnit: A
Note: Value can be positive or negative.
Positive Sequence Current
Positive Sequence Current consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
Symbol: I1
Measurement: Electric CurrentUnit: A
Note: Value can be positive or negative.
Negative Sequence Impedance
Negative Sequence Impedance consists of balanced three-phase impedance phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
Symbol: Z2
Measurement: Electric ResistanceUnit: Ω
Note: Value can be positive or negative.
Zero Sequence Impedance
Zero Sequence Impedance consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counter clockwise together.
Symbol: Z0
Measurement: Electric ResistanceUnit: Ω
Note: Value can be positive or negative.
Fault Impedance
Fault Impedance is a measure of the resistance and reactance in an electrical circuit that is used to calculate the fault current that flows through the circuit in the event of a fault.
Symbol: Zf
Measurement: Electric ResistanceUnit: Ω
Note: Value should be greater than 0.

Other Formulas to find Zero Sequence Current

​Go Zero Sequence Current using B-Phase Voltage (LLGF)
I0=Vb3Zf
​Go Zero Sequence Current using C-Phase Voltage (LLGF)
I0=Vc3Zf
​Go Zero Sequence Current using Zero Sequence Voltage (LLGF)
I0=(-1)V0Z0
​Go Zero Sequence Current using Sequence Voltages and Fault Impedance(LLGF)
I0=V0-V13Zf

Other formulas in Current category

​Go B-Phase Current (LLGF)
Ib=If-Ic
​Go C-Phase Current (LLGF)
Ic=If-Ib
​Go Fault Current (LLGF)
If=Ib+Ic
​Go Fault Current using B-Phase Voltage (LLGF)
If=VbZf

How to Evaluate Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?

Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) evaluator uses Zero Sequence Current = -Positive Sequence Current*((Negative Sequence Impedance)/(Zero Sequence Impedance+Negative Sequence Impedance+3*Fault Impedance)) to evaluate the Zero Sequence Current, The Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) formula consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation. Zero Sequence Current is denoted by I0 symbol.

How to evaluate Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) using this online evaluator? To use this online evaluator for Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF), enter Positive Sequence Current (I1), Negative Sequence Impedance (Z2), Zero Sequence Impedance (Z0) & Fault Impedance (Zf) and hit the calculate button.

FAQs on Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)

What is the formula to find Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?
The formula of Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) is expressed as Zero Sequence Current = -Positive Sequence Current*((Negative Sequence Impedance)/(Zero Sequence Impedance+Negative Sequence Impedance+3*Fault Impedance)). Here is an example- -1.562953 = -2.001*(((-44.6))/(8+(-44.6)+3*1.5)).
How to calculate Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?
With Positive Sequence Current (I1), Negative Sequence Impedance (Z2), Zero Sequence Impedance (Z0) & Fault Impedance (Zf) we can find Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) using the formula - Zero Sequence Current = -Positive Sequence Current*((Negative Sequence Impedance)/(Zero Sequence Impedance+Negative Sequence Impedance+3*Fault Impedance)).
What are the other ways to Calculate Zero Sequence Current?
Here are the different ways to Calculate Zero Sequence Current-
  • Zero Sequence Current=B Phase Voltage/(3*Fault Impedance)OpenImg
  • Zero Sequence Current=C Phase Voltage/(3*Fault Impedance)OpenImg
  • Zero Sequence Current=(-1)*Zero Sequence Voltage/Zero Sequence ImpedanceOpenImg
Can the Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) be negative?
Yes, the Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF), measured in Electric Current can be negative.
Which unit is used to measure Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?
Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) is usually measured using the Ampere[A] for Electric Current. Milliampere[A], Microampere[A], Centiampere[A] are the few other units in which Zero Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) can be measured.
Copied!