Oxygen Required is the amount of oxygen needed to sustain biological processes in an aeration tank, which is a critical component of wastewater treatment systems. Check FAQs
Or=(Qs(Qi-Q)BOD5BODu)-(1.42QwXR)
Or - Oxygen Required?Qs - Sewage Discharge?Qi - Influent BOD?Q - Effluent BOD?BOD5 - 5 Days BOD?BODu - Ultimate BOD?Qw - Volume of Wasted Sludge per day?XR - MLSS in Returned or Wasted Sludge?

Oxygen Required in Aeration Tank given Ultimate BOD Example

With values
With units
Only example

Here is how the Oxygen Required in Aeration Tank given Ultimate BOD equation looks like with Values.

Here is how the Oxygen Required in Aeration Tank given Ultimate BOD equation looks like with Units.

Here is how the Oxygen Required in Aeration Tank given Ultimate BOD equation looks like.

0.1693Edit=(10Edit(13.2Edit-0.4Edit)1.36Edit2Edit)-(1.429.5Edit1.4Edit)
You are here -
HomeIcon Home » Category Engineering » Category Civil » Category Environmental Engineering » fx Oxygen Required in Aeration Tank given Ultimate BOD

Oxygen Required in Aeration Tank given Ultimate BOD Solution

Follow our step by step solution on how to calculate Oxygen Required in Aeration Tank given Ultimate BOD?

FIRST Step Consider the formula
Or=(Qs(Qi-Q)BOD5BODu)-(1.42QwXR)
Next Step Substitute values of Variables
Or=(10m³/s(13.2mg/L-0.4mg/L)1.36mg/L2mg/L)-(1.429.5m³/s1.4mg/L)
Next Step Convert Units
Or=(10m³/s(0.0132kg/m³-0.0004kg/m³)0.0014kg/m³0.002kg/m³)-(1.429.5m³/s0.0014kg/m³)
Next Step Prepare to Evaluate
Or=(10(0.0132-0.0004)0.00140.002)-(1.429.50.0014)
Next Step Evaluate
Or=1.9600612745098E-12kg/s
Next Step Convert to Output's Unit
Or=0.169349294117647mg/d
LAST Step Rounding Answer
Or=0.1693mg/d

Oxygen Required in Aeration Tank given Ultimate BOD Formula Elements

Variables
Oxygen Required
Oxygen Required is the amount of oxygen needed to sustain biological processes in an aeration tank, which is a critical component of wastewater treatment systems.
Symbol: Or
Measurement: Mass Flow RateUnit: mg/d
Note: Value should be greater than 0.
Sewage Discharge
Sewage Discharge is the flow rate of sewage when it is being discharged in the river.
Symbol: Qs
Measurement: Volumetric Flow RateUnit: m³/s
Note: Value should be greater than 0.
Influent BOD
Influent BOD is the total amount of BOD which is present in the incoming sewage.
Symbol: Qi
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.
Effluent BOD
Effluent BOD is the amount of BOD present in the outing sewage.
Symbol: Q
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.
5 Days BOD
5 Days BOD is an indicator of how much oxygen is utilized by a natural water sample in five days at 20 degrees C.
Symbol: BOD5
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.
Ultimate BOD
Ultimate BOD is the amount of oxygen required to decompose all of the organic material after infinite time.
Symbol: BODu
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.
Volume of Wasted Sludge per day
Volume of Wasted Sludge per day is the amount of sludge that is removed or wasted from a wastewater treatment process on a daily basis.
Symbol: Qw
Measurement: Volumetric Flow RateUnit: m³/s
Note: Value should be greater than 0.
MLSS in Returned or Wasted Sludge
MLSS in Returned or Wasted Sludge is the mixed liquor suspended solids in returned sludge in terms of mg per liter.
Symbol: XR
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.

Other Formulas to find Oxygen Required

​Go Oxygen Required in Aeration Tank given Oxygen Demand and Ultimate BOD
Or=(Qs(Qi-Q)BOD5BODu)-(DO2QwXR)

Other formulas in Oxygen Required in Aeration Tank category

​Go Oxygen Required in Aeration Tank
Oa=(Qs(Qi-Q)f)-(1.42QwXR)
​Go Oxygen Required in Aeration Tank given Oxygen Demand of Biomass
Oa=(Qs(Qi-Q)f)-(DO2QwXR)

How to Evaluate Oxygen Required in Aeration Tank given Ultimate BOD?

Oxygen Required in Aeration Tank given Ultimate BOD evaluator uses Oxygen Required = ((Sewage Discharge*(Influent BOD-Effluent BOD))/(5 Days BOD/Ultimate BOD))-(1.42*Volume of Wasted Sludge per day*MLSS in Returned or Wasted Sludge) to evaluate the Oxygen Required, The Oxygen Required in Aeration Tank given Ultimate BOD formula is defined as the calculation of oxygen required in aeration tank when we have prior information of Ultimate BOD. Oxygen Required is denoted by Or symbol.

How to evaluate Oxygen Required in Aeration Tank given Ultimate BOD using this online evaluator? To use this online evaluator for Oxygen Required in Aeration Tank given Ultimate BOD, enter Sewage Discharge (Qs), Influent BOD (Qi), Effluent BOD (Q), 5 Days BOD (BOD5), Ultimate BOD (BODu), Volume of Wasted Sludge per day (Qw) & MLSS in Returned or Wasted Sludge (XR) and hit the calculate button.

FAQs on Oxygen Required in Aeration Tank given Ultimate BOD

What is the formula to find Oxygen Required in Aeration Tank given Ultimate BOD?
The formula of Oxygen Required in Aeration Tank given Ultimate BOD is expressed as Oxygen Required = ((Sewage Discharge*(Influent BOD-Effluent BOD))/(5 Days BOD/Ultimate BOD))-(1.42*Volume of Wasted Sludge per day*MLSS in Returned or Wasted Sludge). Here is an example- 1.5E+10 = ((10*(0.0132-0.0004))/(0.00136/0.002))-(1.42*9.5*0.0014).
How to calculate Oxygen Required in Aeration Tank given Ultimate BOD?
With Sewage Discharge (Qs), Influent BOD (Qi), Effluent BOD (Q), 5 Days BOD (BOD5), Ultimate BOD (BODu), Volume of Wasted Sludge per day (Qw) & MLSS in Returned or Wasted Sludge (XR) we can find Oxygen Required in Aeration Tank given Ultimate BOD using the formula - Oxygen Required = ((Sewage Discharge*(Influent BOD-Effluent BOD))/(5 Days BOD/Ultimate BOD))-(1.42*Volume of Wasted Sludge per day*MLSS in Returned or Wasted Sludge).
What are the other ways to Calculate Oxygen Required?
Here are the different ways to Calculate Oxygen Required-
  • Oxygen Required=((Sewage Discharge*(Influent BOD-Effluent BOD))/(5 Days BOD/Ultimate BOD))-(Oxygen Demand of Biomass*Volume of Wasted Sludge per day*MLSS in Returned or Wasted Sludge)OpenImg
Can the Oxygen Required in Aeration Tank given Ultimate BOD be negative?
No, the Oxygen Required in Aeration Tank given Ultimate BOD, measured in Mass Flow Rate cannot be negative.
Which unit is used to measure Oxygen Required in Aeration Tank given Ultimate BOD?
Oxygen Required in Aeration Tank given Ultimate BOD is usually measured using the Milligram per Day[mg/d] for Mass Flow Rate. Kilogram per Second[mg/d], Gram per Second[mg/d], Gram per Hour[mg/d] are the few other units in which Oxygen Required in Aeration Tank given Ultimate BOD can be measured.
Copied!