Fx Copy
LaTeX Copy
Negative Sequence Current consists of balanced three-phase current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation. Check FAQs
I2=-I1(Z0+3ZfZ0+Z2+3Zf)
I2 - Negative Sequence Current?I1 - Positive Sequence Current?Z0 - Zero Sequence Impedance?Zf - Fault Impedance?Z2 - Negative Sequence Impedance?

Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) Example

With values
With units
Only example

Here is how the Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) equation looks like with Values.

Here is how the Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) equation looks like with Units.

Here is how the Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) equation looks like.

0.7792Edit=-2.001Edit(8Edit+31.5Edit8Edit+-44.6Edit+31.5Edit)
You are here -

Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) Solution

Follow our step by step solution on how to calculate Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?

FIRST Step Consider the formula
I2=-I1(Z0+3ZfZ0+Z2+3Zf)
Next Step Substitute values of Variables
I2=-2.001A(8Ω+31.5Ω8Ω+-44.6Ω+31.5Ω)
Next Step Prepare to Evaluate
I2=-2.001(8+31.58+-44.6+31.5)
Next Step Evaluate
I2=0.779205607476635A
LAST Step Rounding Answer
I2=0.7792A

Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) Formula Elements

Variables
Negative Sequence Current
Negative Sequence Current consists of balanced three-phase current phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
Symbol: I2
Measurement: Electric CurrentUnit: A
Note: Value can be positive or negative.
Positive Sequence Current
Positive Sequence Current consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
Symbol: I1
Measurement: Electric CurrentUnit: A
Note: Value can be positive or negative.
Zero Sequence Impedance
Zero Sequence Impedance consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counter clockwise together.
Symbol: Z0
Measurement: Electric ResistanceUnit: Ω
Note: Value can be positive or negative.
Fault Impedance
Fault Impedance is a measure of the resistance and reactance in an electrical circuit that is used to calculate the fault current that flows through the circuit in the event of a fault.
Symbol: Zf
Measurement: Electric ResistanceUnit: Ω
Note: Value should be greater than 0.
Negative Sequence Impedance
Negative Sequence Impedance consists of balanced three-phase impedance phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
Symbol: Z2
Measurement: Electric ResistanceUnit: Ω
Note: Value can be positive or negative.

Other Formulas to find Negative Sequence Current

​Go Negative Sequence Current using Negative Sequence Voltage (LLGF)
I2=(-1)V2Z2

Other formulas in Current category

​Go B-Phase Current (LLGF)
Ib=If-Ic
​Go C-Phase Current (LLGF)
Ic=If-Ib
​Go Fault Current (LLGF)
If=Ib+Ic
​Go Fault Current using B-Phase Voltage (LLGF)
If=VbZf

How to Evaluate Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?

Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) evaluator uses Negative Sequence Current = -Positive Sequence Current*((Zero Sequence Impedance+3*Fault Impedance)/(Zero Sequence Impedance+Negative Sequence Impedance+3*Fault Impedance)) to evaluate the Negative Sequence Current, The Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) formula is defined as a concept in electrical engineering that refers to the flow of electric current in a three-phase power system where all three phases have the same magnitude and are equally spaced in phase angle. Negative Sequence Current is denoted by I2 symbol.

How to evaluate Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) using this online evaluator? To use this online evaluator for Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF), enter Positive Sequence Current (I1), Zero Sequence Impedance (Z0), Fault Impedance (Zf) & Negative Sequence Impedance (Z2) and hit the calculate button.

FAQs on Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)

What is the formula to find Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?
The formula of Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) is expressed as Negative Sequence Current = -Positive Sequence Current*((Zero Sequence Impedance+3*Fault Impedance)/(Zero Sequence Impedance+Negative Sequence Impedance+3*Fault Impedance)). Here is an example- -0.438047 = -2.001*((8+3*1.5)/(8+(-44.6)+3*1.5)).
How to calculate Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?
With Positive Sequence Current (I1), Zero Sequence Impedance (Z0), Fault Impedance (Zf) & Negative Sequence Impedance (Z2) we can find Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) using the formula - Negative Sequence Current = -Positive Sequence Current*((Zero Sequence Impedance+3*Fault Impedance)/(Zero Sequence Impedance+Negative Sequence Impedance+3*Fault Impedance)).
What are the other ways to Calculate Negative Sequence Current?
Here are the different ways to Calculate Negative Sequence Current-
  • Negative Sequence Current=(-1)*Negative Sequence Voltage/Negative Sequence ImpedanceOpenImg
Can the Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) be negative?
Yes, the Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF), measured in Electric Current can be negative.
Which unit is used to measure Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF)?
Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) is usually measured using the Ampere[A] for Electric Current. Milliampere[A], Microampere[A], Centiampere[A] are the few other units in which Negative Sequence Current using Positive Sequence Current and Sequence Impedances(LLGF) can be measured.
Copied!