Influent BOD given Specific Substrate Utilization Rate Per Day Formula

Fx Copy
LaTeX Copy
Influent BOD given Substrate Utilization Rate is the measure of the organic load entering a wastewater treatment system based on the rate at which microorganisms consume organic matter. Check FAQs
Qi'=(UVX'Qs)+Qo
Qi' - Influent BOD given Substrate Utilization Rate?U - Specific Substrate Utilization Rate?V - Volume of Tank?X' - Mixed Liquor Suspended Solids?Qs - Sewage Discharge?Qo - Effluent BOD?

Influent BOD given Specific Substrate Utilization Rate Per Day Example

With values
With units
Only example

Here is how the Influent BOD given Specific Substrate Utilization Rate Per Day equation looks like with Values.

Here is how the Influent BOD given Specific Substrate Utilization Rate Per Day equation looks like with Units.

Here is how the Influent BOD given Specific Substrate Utilization Rate Per Day equation looks like.

540.4Edit=(0.5Edit9Edit1200Edit10Edit)+0.4Edit
You are here -
HomeIcon Home » Category Engineering » Category Civil » Category Environmental Engineering » fx Influent BOD given Specific Substrate Utilization Rate Per Day

Influent BOD given Specific Substrate Utilization Rate Per Day Solution

Follow our step by step solution on how to calculate Influent BOD given Specific Substrate Utilization Rate Per Day?

FIRST Step Consider the formula
Qi'=(UVX'Qs)+Qo
Next Step Substitute values of Variables
Qi'=(0.5s⁻¹91200mg/L10m³/s)+0.4mg/L
Next Step Convert Units
Qi'=(0.5s⁻¹91.2kg/m³10m³/s)+0.0004kg/m³
Next Step Prepare to Evaluate
Qi'=(0.591.210)+0.0004
Next Step Evaluate
Qi'=0.5404kg/m³
LAST Step Convert to Output's Unit
Qi'=540.4mg/L

Influent BOD given Specific Substrate Utilization Rate Per Day Formula Elements

Variables
Influent BOD given Substrate Utilization Rate
Influent BOD given Substrate Utilization Rate is the measure of the organic load entering a wastewater treatment system based on the rate at which microorganisms consume organic matter.
Symbol: Qi'
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.
Specific Substrate Utilization Rate
Specific Substrate Utilization Rate is the rate at which a microbial population consumes a substrate per unit of biomass present.
Symbol: U
Measurement: First Order Reaction Rate ConstantUnit: s⁻¹
Note: Value should be greater than 0.
Volume of Tank
Volume of Tank is defined as the capacity of flocculation and mixing tank.
Symbol: V
Measurement: VolumeUnit:
Note: Value should be greater than 0.
Mixed Liquor Suspended Solids
Mixed Liquor Suspended Solids is the concentration of suspended solids in the mixed liquor of an aeration tank during the activated sludge process.
Symbol: X'
Measurement: DensityUnit: mg/L
Note: Value should be between 1000 to 6500.
Sewage Discharge
Sewage Discharge is the flow rate of sewage when it is being discharged in the river.
Symbol: Qs
Measurement: Volumetric Flow RateUnit: m³/s
Note: Value should be greater than 0.
Effluent BOD
Effluent BOD is the amount of BOD present in the outing sewage.
Symbol: Qo
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.

Other formulas in Influent and Effluent BOD category

​Go Influent BOD given Mass of Wasted Activated Sludge
Qi=(Mws+(KeVX')YQs)+Qo
​Go Effluent BOD given Mass of Wasted Activated Sludge
Qo=Qi-(Mws+(KeVX')YQs)

How to Evaluate Influent BOD given Specific Substrate Utilization Rate Per Day?

Influent BOD given Specific Substrate Utilization Rate Per Day evaluator uses Influent BOD given Substrate Utilization Rate = ((Specific Substrate Utilization Rate*Volume of Tank*Mixed Liquor Suspended Solids)/Sewage Discharge)+Effluent BOD to evaluate the Influent BOD given Substrate Utilization Rate, The Influent BOD given Specific Substrate Utilization Rate Per Day formula is defined as the calculation of influent BOD when we have prior information of specific substrate utilization rate per day. Influent BOD given Substrate Utilization Rate is denoted by Qi' symbol.

How to evaluate Influent BOD given Specific Substrate Utilization Rate Per Day using this online evaluator? To use this online evaluator for Influent BOD given Specific Substrate Utilization Rate Per Day, enter Specific Substrate Utilization Rate (U), Volume of Tank (V), Mixed Liquor Suspended Solids (X'), Sewage Discharge (Qs) & Effluent BOD (Qo) and hit the calculate button.

FAQs on Influent BOD given Specific Substrate Utilization Rate Per Day

What is the formula to find Influent BOD given Specific Substrate Utilization Rate Per Day?
The formula of Influent BOD given Specific Substrate Utilization Rate Per Day is expressed as Influent BOD given Substrate Utilization Rate = ((Specific Substrate Utilization Rate*Volume of Tank*Mixed Liquor Suspended Solids)/Sewage Discharge)+Effluent BOD. Here is an example- 540400 = ((0.5*9*1.2)/10)+0.0004.
How to calculate Influent BOD given Specific Substrate Utilization Rate Per Day?
With Specific Substrate Utilization Rate (U), Volume of Tank (V), Mixed Liquor Suspended Solids (X'), Sewage Discharge (Qs) & Effluent BOD (Qo) we can find Influent BOD given Specific Substrate Utilization Rate Per Day using the formula - Influent BOD given Substrate Utilization Rate = ((Specific Substrate Utilization Rate*Volume of Tank*Mixed Liquor Suspended Solids)/Sewage Discharge)+Effluent BOD.
Can the Influent BOD given Specific Substrate Utilization Rate Per Day be negative?
No, the Influent BOD given Specific Substrate Utilization Rate Per Day, measured in Density cannot be negative.
Which unit is used to measure Influent BOD given Specific Substrate Utilization Rate Per Day?
Influent BOD given Specific Substrate Utilization Rate Per Day is usually measured using the Milligram per Liter[mg/L] for Density. Kilogram per Cubic Meter[mg/L], Kilogram per Cubic Centimeter[mg/L], Gram per Cubic Meter[mg/L] are the few other units in which Influent BOD given Specific Substrate Utilization Rate Per Day can be measured.
Copied!