The effectiveness of heat exchanger is defined as the ratio of the actual heat transfer to the maximum possible heat transfer. Check FAQs
ϵ=(1C)(1-exp(-1C(1-exp(-1NTU))))
ϵ - Effectiveness of Heat Exchanger?C - Heat capacity ratio?NTU - Number of Transfer Units?

Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed Example

With values
With units
Only example

Here is how the Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed equation looks like with Values.

Here is how the Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed equation looks like with Units.

Here is how the Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed equation looks like.

0.7869Edit=(10.5Edit)(1-exp(-10.5Edit(1-exp(-112Edit))))
You are here -
HomeIcon Home » Category Physics » Category Mechanical » Category Heat and Mass Transfer » fx Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed

Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed Solution

Follow our step by step solution on how to calculate Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed?

FIRST Step Consider the formula
ϵ=(1C)(1-exp(-1C(1-exp(-1NTU))))
Next Step Substitute values of Variables
ϵ=(10.5)(1-exp(-10.5(1-exp(-112))))
Next Step Prepare to Evaluate
ϵ=(10.5)(1-exp(-10.5(1-exp(-112))))
Next Step Evaluate
ϵ=0.786934953915837
LAST Step Rounding Answer
ϵ=0.7869

Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed Formula Elements

Variables
Functions
Effectiveness of Heat Exchanger
The effectiveness of heat exchanger is defined as the ratio of the actual heat transfer to the maximum possible heat transfer.
Symbol: ϵ
Measurement: NAUnit: Unitless
Note: Value should be greater than 0.
Heat capacity ratio
Heat capacity ratio is the ratio of cmin and cmax.
Symbol: C
Measurement: NAUnit: Unitless
Note: Value can be positive or negative.
Number of Transfer Units
The number of transfer units is defined as ratio of overall thermal conductance to smaller heat capacity rate. NTU designates non-dimensional heat transfer size or thermal size of the exchanger.
Symbol: NTU
Measurement: NAUnit: Unitless
Note: Value should be greater than 0.
exp
n an exponential function, the value of the function changes by a constant factor for every unit change in the independent variable.
Syntax: exp(Number)

Other Formulas to find Effectiveness of Heat Exchanger

​Go Effectiveness NTU method
ϵ=QCmin(T1-t1)
​Go Effectiveness in double pipe parallel flow heat exchanger
ϵ=1-exp(-1NTU(1+C))1+C
​Go Effectiveness of double pipe counter flow heat exchanger
ϵ=1-exp(-1NTU(1-C))1-Cexp(-1NTU(1-C))
​Go Effectiveness of double pipe counter flow heat exchanger given C equal to 1
ϵ=NTU1+NTU

How to Evaluate Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed?

Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed evaluator uses Effectiveness of Heat Exchanger = (1/Heat capacity ratio)*(1-exp(-1*Heat capacity ratio*(1-exp(-1*Number of Transfer Units)))) to evaluate the Effectiveness of Heat Exchanger, The Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed formula is defined as the ratio of the actual heat transfer to the maximum possible heat transfer. Effectiveness of Heat Exchanger is denoted by ϵ symbol.

How to evaluate Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed using this online evaluator? To use this online evaluator for Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed, enter Heat capacity ratio (C) & Number of Transfer Units (NTU) and hit the calculate button.

FAQs on Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed

What is the formula to find Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed?
The formula of Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed is expressed as Effectiveness of Heat Exchanger = (1/Heat capacity ratio)*(1-exp(-1*Heat capacity ratio*(1-exp(-1*Number of Transfer Units)))). Here is an example- 0.786935 = (1/0.5)*(1-exp(-1*0.5*(1-exp(-1*12)))).
How to calculate Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed?
With Heat capacity ratio (C) & Number of Transfer Units (NTU) we can find Effectiveness of heat exchanger when Cmax is mixed and Cmin is unmixed using the formula - Effectiveness of Heat Exchanger = (1/Heat capacity ratio)*(1-exp(-1*Heat capacity ratio*(1-exp(-1*Number of Transfer Units)))). This formula also uses Exponential Growth (exp) function(s).
What are the other ways to Calculate Effectiveness of Heat Exchanger?
Here are the different ways to Calculate Effectiveness of Heat Exchanger-
  • Effectiveness of Heat Exchanger=Heat exchanged/(Smaller Value*(Entry Temperature of Hot Fluid-Entry Temperature of Cold Fluid))OpenImg
  • Effectiveness of Heat Exchanger=(1-exp(-1*Number of Transfer Units*(1+Heat capacity ratio)))/(1+Heat capacity ratio)OpenImg
  • Effectiveness of Heat Exchanger=(1-exp(-1*Number of Transfer Units*(1-Heat capacity ratio)))/(1-Heat capacity ratio*exp(-1*Number of Transfer Units*(1-Heat capacity ratio)))OpenImg
Copied!