Dissolved Oxygen Saturation for Sewage Formula

Fx Copy
LaTeX Copy
Dissolved Oxygen Saturation is the maximum amount of oxygen that can be dissolved in water at a given temperature and pressure. Check FAQs
DS=(N9.17NsCf(1.024)T-20)+DL
DS - Dissolved Oxygen Saturation?N - Oxygen Transferred?Ns - Oxygen Transfer Capacity?Cf - Correction Factor?T - Temperature?DL - Operation Dissolved Oxygen?

Dissolved Oxygen Saturation for Sewage Example

With values
With units
Only example

Here is how the Dissolved Oxygen Saturation for Sewage equation looks like with Values.

Here is how the Dissolved Oxygen Saturation for Sewage equation looks like with Units.

Here is how the Dissolved Oxygen Saturation for Sewage equation looks like.

5803.3373Edit=(3Edit9.172.03Edit0.5Edit(1.024)85Edit-20)+2.01Edit
You are here -
HomeIcon Home » Category Engineering » Category Civil » Category Environmental Engineering » fx Dissolved Oxygen Saturation for Sewage

Dissolved Oxygen Saturation for Sewage Solution

Follow our step by step solution on how to calculate Dissolved Oxygen Saturation for Sewage?

FIRST Step Consider the formula
DS=(N9.17NsCf(1.024)T-20)+DL
Next Step Substitute values of Variables
DS=(3kg/h/kW9.172.03kg/h/kW0.5(1.024)85K-20)+2.01mg/L
Next Step Convert Units
DS=(8.3E-7kg/s/W9.175.6E-7kg/s/W0.5(1.024)85K-20)+0.002kg/m³
Next Step Prepare to Evaluate
DS=(8.3E-79.175.6E-70.5(1.024)85-20)+0.002
Next Step Evaluate
DS=5.80333727748047kg/m³
Next Step Convert to Output's Unit
DS=5803.33727748047mg/L
LAST Step Rounding Answer
DS=5803.3373mg/L

Dissolved Oxygen Saturation for Sewage Formula Elements

Variables
Dissolved Oxygen Saturation
Dissolved Oxygen Saturation is the maximum amount of oxygen that can be dissolved in water at a given temperature and pressure.
Symbol: DS
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.
Oxygen Transferred
Oxygen Transferred is the amount of oxygen that is moved from the air into the water.
Symbol: N
Measurement: Specific Fuel ConsumptionUnit: kg/h/kW
Note: Value should be greater than 0.
Oxygen Transfer Capacity
Oxygen Transfer Capacity is the ability of a system, typically in a wastewater treatment context, to transfer oxygen from the air into the water.
Symbol: Ns
Measurement: Specific Fuel ConsumptionUnit: kg/h/kW
Note: Value should be greater than 0.
Correction Factor
Correction Factor is that which is multiplied with the result of an equation to correct for a known amount of systematic error.
Symbol: Cf
Measurement: NAUnit: Unitless
Note: Value can be positive or negative.
Temperature
Temperature is the degree or intensity of heat present in a substance or object.
Symbol: T
Measurement: TemperatureUnit: K
Note: Value can be positive or negative.
Operation Dissolved Oxygen
Operation Dissolved Oxygen is the amount of oxygen that is present in water. It is a crucial parameter in assessing water quality because it is essential for the survival of aquatic organisms.
Symbol: DL
Measurement: DensityUnit: mg/L
Note: Value should be greater than 0.

Other formulas in D.O Saturation category

​Go Ratio of BOD to Ultimate BOD
f=BOD5BODu
​Go BOD5 given Oxygen Required in Aeration Tank
BOD5a=BODuQs(Qi-Q)O2+(1.42QwXR)
​Go BOD5 given Ratio of BOD to Ultimate BOD
BOD5r=fBODu
​Go BOD5 when Ratio of BOD to Ultimate BOD is 0.68
BOD5=BODu0.68

How to Evaluate Dissolved Oxygen Saturation for Sewage?

Dissolved Oxygen Saturation for Sewage evaluator uses Dissolved Oxygen Saturation = ((Oxygen Transferred*9.17)/(Oxygen Transfer Capacity*Correction Factor*(1.024)^(Temperature-20)))+Operation Dissolved Oxygen to evaluate the Dissolved Oxygen Saturation, Dissolved Oxygen Saturation for Sewage formula is defined as a measure of the percentage of dissolved oxygen in sewage water, which is essential for the survival of aquatic life and indicates the level of oxygen available for microorganisms to break down organic matter during the aeration process. Dissolved Oxygen Saturation is denoted by DS symbol.

How to evaluate Dissolved Oxygen Saturation for Sewage using this online evaluator? To use this online evaluator for Dissolved Oxygen Saturation for Sewage, enter Oxygen Transferred (N), Oxygen Transfer Capacity (Ns), Correction Factor (Cf), Temperature (T) & Operation Dissolved Oxygen (DL) and hit the calculate button.

FAQs on Dissolved Oxygen Saturation for Sewage

What is the formula to find Dissolved Oxygen Saturation for Sewage?
The formula of Dissolved Oxygen Saturation for Sewage is expressed as Dissolved Oxygen Saturation = ((Oxygen Transferred*9.17)/(Oxygen Transfer Capacity*Correction Factor*(1.024)^(Temperature-20)))+Operation Dissolved Oxygen. Here is an example- 6.6E+6 = ((8.33333333333333E-07*9.17)/(5.63888888888889E-07*0.5*(1.024)^(85-20)))+0.00201.
How to calculate Dissolved Oxygen Saturation for Sewage?
With Oxygen Transferred (N), Oxygen Transfer Capacity (Ns), Correction Factor (Cf), Temperature (T) & Operation Dissolved Oxygen (DL) we can find Dissolved Oxygen Saturation for Sewage using the formula - Dissolved Oxygen Saturation = ((Oxygen Transferred*9.17)/(Oxygen Transfer Capacity*Correction Factor*(1.024)^(Temperature-20)))+Operation Dissolved Oxygen.
Can the Dissolved Oxygen Saturation for Sewage be negative?
No, the Dissolved Oxygen Saturation for Sewage, measured in Density cannot be negative.
Which unit is used to measure Dissolved Oxygen Saturation for Sewage?
Dissolved Oxygen Saturation for Sewage is usually measured using the Milligram per Liter[mg/L] for Density. Kilogram per Cubic Meter[mg/L], Kilogram per Cubic Centimeter[mg/L], Gram per Cubic Meter[mg/L] are the few other units in which Dissolved Oxygen Saturation for Sewage can be measured.
Copied!