Fx Copy
LaTeX Copy
Constant Underground AC is defined as the constant of line of a Overhead supply system. Check FAQs
K=2(I2)(cos(Φ)2)ρL2Ploss
K - Constant Underground AC?I - Current Underground AC?Φ - Phase Difference?ρ - Resistivity?L - Length of Underground AC Wire?Ploss - Line Losses?

Constant using Load Current (1-Phase 2-Wire US) Example

With values
With units
Only example

Here is how the Constant using Load Current (1-Phase 2-Wire US) equation looks like with Values.

Here is how the Constant using Load Current (1-Phase 2-Wire US) equation looks like with Units.

Here is how the Constant using Load Current (1-Phase 2-Wire US) equation looks like.

0.4456Edit=2(9Edit2)(cos(30Edit)2)1.7E-5Edit24Edit22.67Edit
You are here -
HomeIcon Home » Category Engineering » Category Electrical » Category Power System » fx Constant using Load Current (1-Phase 2-Wire US)

Constant using Load Current (1-Phase 2-Wire US) Solution

Follow our step by step solution on how to calculate Constant using Load Current (1-Phase 2-Wire US)?

FIRST Step Consider the formula
K=2(I2)(cos(Φ)2)ρL2Ploss
Next Step Substitute values of Variables
K=2(9A2)(cos(30°)2)1.7E-5Ω*m24m22.67W
Next Step Convert Units
K=2(9A2)(cos(0.5236rad)2)1.7E-5Ω*m24m22.67W
Next Step Prepare to Evaluate
K=2(92)(cos(0.5236)2)1.7E-52422.67
Next Step Evaluate
K=0.445591011235955
LAST Step Rounding Answer
K=0.4456

Constant using Load Current (1-Phase 2-Wire US) Formula Elements

Variables
Functions
Constant Underground AC
Constant Underground AC is defined as the constant of line of a Overhead supply system.
Symbol: K
Measurement: NAUnit: Unitless
Note: Value can be positive or negative.
Current Underground AC
Current Underground AC is defined as the current flowing through the overhead ac supply wire.
Symbol: I
Measurement: Electric CurrentUnit: A
Note: Value can be positive or negative.
Phase Difference
Phase Difference is defined as the difference between the phasor of apparent and real power (in degrees) or between voltage and current in an ac circuit.
Symbol: Φ
Measurement: AngleUnit: °
Note: Value should be greater than 0.
Resistivity
Resistivity is the measure of how strongly a material opposes the flow of current through them.
Symbol: ρ
Measurement: Electric ResistivityUnit: Ω*m
Note: Value can be positive or negative.
Length of Underground AC Wire
Length of Underground AC Wire is the total length of the wire from one end to other end.
Symbol: L
Measurement: LengthUnit: m
Note: Value should be greater than 0.
Line Losses
Line Losses is defined as the total losses occurring in an Underground AC line when in use.
Symbol: Ploss
Measurement: PowerUnit: W
Note: Value can be positive or negative.
cos
Cosine of an angle is the ratio of the side adjacent to the angle to the hypotenuse of the triangle.
Syntax: cos(Angle)

Other Formulas to find Constant Underground AC

​Go Constant (1-Phase 2-Wire US)
K=4ρ(PL)2Ploss(Vm)2
​Go Constant using Area of X-Section (1-Phase 2-Wire US)
K=AL(cos(Φ))2
​Go Constant using Volume of Conductor Material (1-Phase 2-Wire US)
K=V(cos(Φ))22
​Go Constant using Line Losses (1-Phase 2-Wire US)
K=4ρ(PVac)2Ploss(Vm)2

Other formulas in Wire Parameters category

​Go Area of X-Section (1-Phase 2-Wire US)
A=(4)ρL(P)2Ploss(Vmcos(Φ))2
​Go Voltage of Conductor Material (1-Phase 2-Wire US)
V=2K(cos(Φ))2
​Go Area of X-Section using Volume of Conductor Material (1-Phase 2-Wire US)
A=V2L
​Go Length using Area of X-Section (1-Phase 2-Wire US)
L=APloss(Vmcos(Φ))24(P2)ρ

How to Evaluate Constant using Load Current (1-Phase 2-Wire US)?

Constant using Load Current (1-Phase 2-Wire US) evaluator uses Constant Underground AC = 2*(Current Underground AC^2)*(cos(Phase Difference)^2)*Resistivity*(Length of Underground AC Wire^2)/Line Losses to evaluate the Constant Underground AC, The Constant using Load Current (1-Phase 2-Wire US) formula is defined as the total constant of a single-phase two-wire overhead system. it is represented by K. Constant Underground AC is denoted by K symbol.

How to evaluate Constant using Load Current (1-Phase 2-Wire US) using this online evaluator? To use this online evaluator for Constant using Load Current (1-Phase 2-Wire US), enter Current Underground AC (I), Phase Difference (Φ), Resistivity (ρ), Length of Underground AC Wire (L) & Line Losses (Ploss) and hit the calculate button.

FAQs on Constant using Load Current (1-Phase 2-Wire US)

What is the formula to find Constant using Load Current (1-Phase 2-Wire US)?
The formula of Constant using Load Current (1-Phase 2-Wire US) is expressed as Constant Underground AC = 2*(Current Underground AC^2)*(cos(Phase Difference)^2)*Resistivity*(Length of Underground AC Wire^2)/Line Losses. Here is an example- 0.445591 = 2*(9^2)*(cos(0.5235987755982)^2)*1.7E-05*(24^2)/2.67.
How to calculate Constant using Load Current (1-Phase 2-Wire US)?
With Current Underground AC (I), Phase Difference (Φ), Resistivity (ρ), Length of Underground AC Wire (L) & Line Losses (Ploss) we can find Constant using Load Current (1-Phase 2-Wire US) using the formula - Constant Underground AC = 2*(Current Underground AC^2)*(cos(Phase Difference)^2)*Resistivity*(Length of Underground AC Wire^2)/Line Losses. This formula also uses Cosine (cos) function(s).
What are the other ways to Calculate Constant Underground AC?
Here are the different ways to Calculate Constant Underground AC-
  • Constant Underground AC=4*Resistivity*(Power Transmitted*Length of Underground AC Wire)^2/(Line Losses*(Maximum Voltage Underground AC)^2)OpenImg
  • Constant Underground AC=Area of Underground AC Wire*Length of Underground AC Wire*(cos(Phase Difference))^2OpenImg
  • Constant Underground AC=Volume Of Conductor*(cos(Phase Difference))^2/2OpenImg
Copied!