Bundle Diameter for Six Tube Pass Square Pitch in Heat Exchanger evaluator uses Bundle Diameter = Pipe Outer Diameter in Bundle Diameter*(Number of Tubes in Bundle Diameter/0.0402)^(1/2.617) to evaluate the Bundle Diameter, The Bundle Diameter for Six Tube Pass Square Pitch in Heat Exchanger formula is defined as the diameter of the tube bundle with Six/Multiple tube-pass within the heat exchanger having Square pitch layout with the pitch equal to 1.25 times the outer diameter on tube-side. Bundle Diameter is denoted by DBundle symbol.
How to evaluate Bundle Diameter for Six Tube Pass Square Pitch in Heat Exchanger using this online evaluator? To use this online evaluator for Bundle Diameter for Six Tube Pass Square Pitch in Heat Exchanger, enter Pipe Outer Diameter in Bundle Diameter (DiaO) & Number of Tubes in Bundle Diameter (NT) and hit the calculate button.