A-phase Current LG is the current that flows into the a-phase in open conductor fault. Check FAQs
Ia(lg)=Vf(lg)Zf(lg)+((13)(Z0(lg)+Z1(lg)+Z2(lg)))
Ia(lg) - A-Phase Current LG?Vf(lg) - Fault Voltage LG?Zf(lg) - Fault Impedance LG?Z0(lg) - Zero Sequence Impedance LG?Z1(lg) - Positive Sequence Impedance LG?Z2(lg) - Negative Sequence Impedance LG?

A-Phase Current using Fault Voltage and Fault Impedance(LGF) Example

With values
With units
Only example

Here is how the A-Phase Current using Fault Voltage and Fault Impedance(LGF) equation looks like with Values.

Here is how the A-Phase Current using Fault Voltage and Fault Impedance(LGF) equation looks like with Units.

Here is how the A-Phase Current using Fault Voltage and Fault Impedance(LGF) equation looks like.

-1.9247Edit=15.5Edit1.5Edit+((13)(8Edit+7.94Edit+-44.6Edit))
You are here -
HomeIcon Home » Category Engineering » Category Electrical » Category Power System » fx A-Phase Current using Fault Voltage and Fault Impedance(LGF)

A-Phase Current using Fault Voltage and Fault Impedance(LGF) Solution

Follow our step by step solution on how to calculate A-Phase Current using Fault Voltage and Fault Impedance(LGF)?

FIRST Step Consider the formula
Ia(lg)=Vf(lg)Zf(lg)+((13)(Z0(lg)+Z1(lg)+Z2(lg)))
Next Step Substitute values of Variables
Ia(lg)=15.5V1.5Ω+((13)(8Ω+7.94Ω+-44.6Ω))
Next Step Prepare to Evaluate
Ia(lg)=15.51.5+((13)(8+7.94+-44.6))
Next Step Evaluate
Ia(lg)=-1.92466887417219A
LAST Step Rounding Answer
Ia(lg)=-1.9247A

A-Phase Current using Fault Voltage and Fault Impedance(LGF) Formula Elements

Variables
A-Phase Current LG
A-phase Current LG is the current that flows into the a-phase in open conductor fault.
Symbol: Ia(lg)
Measurement: Electric CurrentUnit: A
Note: Value can be positive or negative.
Fault Voltage LG
Fault Voltage LG is defined when an electrical fault occurs and results in the deviation of voltage.
Symbol: Vf(lg)
Measurement: Electric PotentialUnit: V
Note: Value should be greater than 0.
Fault Impedance LG
Fault Impedance LG is a measure of the resistance and reactance in an electrical circuit that is used to calculate the fault current that flows through the circuit in the event of a fault.
Symbol: Zf(lg)
Measurement: Electric ResistanceUnit: Ω
Note: Value should be greater than 0.
Zero Sequence Impedance LG
Zero Sequence Impedance LG consists of a balanced three-phase voltage and current, phasors of which all have the same phase angles and rotate counter clockwise together.
Symbol: Z0(lg)
Measurement: Electric ResistanceUnit: Ω
Note: Value can be positive or negative.
Positive Sequence Impedance LG
Positive Sequence Impedance LG consists of balanced three-phase voltage and current phasors which are exactly at 120 degrees apart rotating counterclockwise in ABC rotation.
Symbol: Z1(lg)
Measurement: Electric ResistanceUnit: Ω
Note: Value should be greater than 0.
Negative Sequence Impedance LG
Negative Sequence Impedance LG consists of balanced three-phase impedance phasors which are exactly at 120 degrees apart rotating counterclockwise in ACB rotation.
Symbol: Z2(lg)
Measurement: Electric ResistanceUnit: Ω
Note: Value can be positive or negative.

Other Formulas to find A-Phase Current LG

​Go A-Phase Current using Positive Sequence Current (LGF)
Ia(lg)=I1(lg)3
​Go A-Phase Current using Negative Sequence Current (LGF)
Ia(lg)=3I2(lg)
​Go A-Phase Current using Zero Sequence Current (LGF)
Ia(lg)=I0(lg)3
​Go A-Phase Current using A-Phase Voltage(LGF)
Ia(lg)=Va(lg)Zf(lg)

Other formulas in Current category

​Go Positive Sequence Current using Fault Impedance(LGF)
I1(lg)=V1(lg)+V2(lg)+V0(lg)3Zf(lg)
​Go Positive Sequence Current using A-Phase Current (LGF)
I1(lg)=Ia(lg)3
​Go Negative Sequence Current using A-Phase Current (LGF)
I2(lg)=Ia(lg)3
​Go Zero Sequence Current using A-Phase Current (LGF)
I0(lg)=Ia(lg)3

How to Evaluate A-Phase Current using Fault Voltage and Fault Impedance(LGF)?

A-Phase Current using Fault Voltage and Fault Impedance(LGF) evaluator uses A-Phase Current LG = Fault Voltage LG/(Fault Impedance LG+((1/3)*(Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG))) to evaluate the A-Phase Current LG, The A-phase current using Fault voltage and Fault Impedance(LGF) formula is defined as the current through any one component comprising a three-phase source or load. here we have taken the a-phase. A-Phase Current LG is denoted by Ia(lg) symbol.

How to evaluate A-Phase Current using Fault Voltage and Fault Impedance(LGF) using this online evaluator? To use this online evaluator for A-Phase Current using Fault Voltage and Fault Impedance(LGF), enter Fault Voltage LG (Vf(lg)), Fault Impedance LG (Zf(lg)), Zero Sequence Impedance LG (Z0(lg)), Positive Sequence Impedance LG (Z1(lg)) & Negative Sequence Impedance LG (Z2(lg)) and hit the calculate button.

FAQs on A-Phase Current using Fault Voltage and Fault Impedance(LGF)

What is the formula to find A-Phase Current using Fault Voltage and Fault Impedance(LGF)?
The formula of A-Phase Current using Fault Voltage and Fault Impedance(LGF) is expressed as A-Phase Current LG = Fault Voltage LG/(Fault Impedance LG+((1/3)*(Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG))). Here is an example- -1.924669 = 15.5/(1.5+((1/3)*(8+7.94+(-44.6)))).
How to calculate A-Phase Current using Fault Voltage and Fault Impedance(LGF)?
With Fault Voltage LG (Vf(lg)), Fault Impedance LG (Zf(lg)), Zero Sequence Impedance LG (Z0(lg)), Positive Sequence Impedance LG (Z1(lg)) & Negative Sequence Impedance LG (Z2(lg)) we can find A-Phase Current using Fault Voltage and Fault Impedance(LGF) using the formula - A-Phase Current LG = Fault Voltage LG/(Fault Impedance LG+((1/3)*(Zero Sequence Impedance LG+Positive Sequence Impedance LG+Negative Sequence Impedance LG))).
What are the other ways to Calculate A-Phase Current LG?
Here are the different ways to Calculate A-Phase Current LG-
  • A-Phase Current LG=Positive Sequence Current LG*3OpenImg
  • A-Phase Current LG=3*Negative Sequence Current LGOpenImg
  • A-Phase Current LG=Zero Sequence Current LG*3OpenImg
Can the A-Phase Current using Fault Voltage and Fault Impedance(LGF) be negative?
Yes, the A-Phase Current using Fault Voltage and Fault Impedance(LGF), measured in Electric Current can be negative.
Which unit is used to measure A-Phase Current using Fault Voltage and Fault Impedance(LGF)?
A-Phase Current using Fault Voltage and Fault Impedance(LGF) is usually measured using the Ampere[A] for Electric Current. Milliampere[A], Microampere[A], Centiampere[A] are the few other units in which A-Phase Current using Fault Voltage and Fault Impedance(LGF) can be measured.
Copied!